12 Volt help what am I doing wrong

Anything electric, AC or DC

12 Volt help what am I doing wrong

Postby Woodbutcher » Tue Nov 28, 2006 11:01 am

I have run 14/2 wire from the rear of my tear up to the front to feed 2 wall sconces and 2 DC sockets. I have a single wire as a power feed. I wanted to use a terminal strip like this.

Image
Image
I have a box buried in my floor and was hoping to get the whole mess into it.
I connected the power wires and all 4 of the other leads. I put in 15 amp fuses and the power lead fuse would blow. I then tried just hooking up the power and 1 light. Blows again. If I take the power lead and the 2 sconce light leads and tie them together without the terminal strip and fuses the lights work. What am I doing wrong and how can I correct it?
User avatar
Woodbutcher
Platinum Donating Member
 
Posts: 4187
Images: 45
Joined: Fri Mar 10, 2006 10:01 pm
Location: Chicago Suburbs

Postby Dale M. » Tue Nov 28, 2006 11:37 am

Your description of the problem is a little confusing.....

You need to verify that each wire has no shorts of cross connections...

You have to have a 12 volt source feeding one side of fuse block (unit you call terminal strip)... The voltage goes through fuse and on to lamp socket. by the "hot" wire ( 12 volt) of the 14/2 pair

Other wire in the 14/2 pair goes from ground source, bypasses fuse block and goes directly to lamp socket....

Image

Dale
Lives his life vicariously through his own self.

Any statement made by me are strictly my own opinion.
You are free to ignore anything I say if you do not agree.

Image
User avatar
Dale M.
2000 Club
2000 Club
 
Posts: 2693
Images: 18
Joined: Thu Jun 09, 2005 8:50 pm
Location: Just a tiny bit west of Yosemite National Park

Postby Woodbutcher » Tue Nov 28, 2006 11:59 am

The wires have black writing on one side of the pair. So I used the black writing side as the ground side through out the project. I ran all ground wires on one side of the terminal and all the power leads to the other. Then I fused each one. I kept ech lead directly acrss from its mate. Now that I typed this explaination out I realized that I completed the neg/pos circuit as soon as I put in a fuse, thus causing a short. Do I use the terminal with out the fuses thus connecting each side only to itself?
User avatar
Woodbutcher
Platinum Donating Member
 
Posts: 4187
Images: 45
Joined: Fri Mar 10, 2006 10:01 pm
Location: Chicago Suburbs
Top

Postby madjack » Tue Nov 28, 2006 12:03 pm

...yep, keep in mind that the fuse block you are using has NO provisions(shown) for ground (or common)...your grounds should all be going back to the 12vdc (negative side) source...other than that, you have a wire crossed/shorted somewhere....
madjack 8)
...I have come to believe that, conflict resolution, through violence, is never acceptable.....................mj
User avatar
madjack
Site Admin
 
Posts: 15128
Images: 177
Joined: Thu Dec 02, 2004 5:27 pm
Location: Central Louisiana
Top

Postby Steve Frederick » Tue Nov 28, 2006 12:20 pm

Get a terminal block without fuses, land all of the common/ground conductors there, then connect the terminal block to the neg side of the battery.
You can get a block that will work at Home Depot, in the crimp connector section, made by Ideal..Image
The drawing by Dale shows the other (hot) side of the system. You'll need to create a "buss" on the side that runs to the battery, like Dale showed on his feed side on his illustration.
Blessings, Steve
Adirondacks, Upstate New York
Building Journals
The Shop Manual's 8-years old!! Thank's everyone!
New! 'Rondack Lodge Plans!Order Here!
Image
User avatar
Steve Frederick
Custom Teardrop Builder
 
Posts: 1984
Images: 29
Joined: Thu Apr 15, 2004 5:02 pm
Location: Upstate New York, Adirondacks (Great Sacandaga Lake)
Top

Postby Woodbutcher » Tue Nov 28, 2006 1:46 pm

Thanks guys ... I got it now. As you can see, electrical is not my strong suit.
User avatar
Woodbutcher
Platinum Donating Member
 
Posts: 4187
Images: 45
Joined: Fri Mar 10, 2006 10:01 pm
Location: Chicago Suburbs
Top

Postby mikeschn » Tue Nov 28, 2006 5:40 pm

Well, I may be too late, but since it seem you are doing the same thing I did, I figured I'd show you my setup again...

http://tnttt.com/viewto ... lock#11309

Mike...
The quality is remembered long after the price is forgotten, so build your teardrop with the best materials...
User avatar
mikeschn
Site Admin
 
Posts: 19202
Images: 479
Joined: Tue Apr 13, 2004 11:01 am
Location: MI
Top

Postby Woodbutcher » Tue Nov 28, 2006 8:56 pm

Thanks Mike! I did get it to work. Your setup is prettier then mine. But it now works. It's only hooked up to a test battery now. I still have my inverter wiring to do. So be ready for some more dumb questions when I get there. I see you have 10W fuses in. It that the best size for the small 12V lights?